GT3-3 is an intelligent emergency power supply that comes with online conversion technology which allows for zero conversion time. In the event of power failure, the GT3-3 Uninterrupted Power Supply with online conversion loads the power to your devices instantly, ensuring uninterrupted operation of your devices.
Model and Capacity | 10K | Capacity: 10KVA/8KW 15K | Capacity: 15KVA/12KW 20K | Capacity: 20KVA/16KW 30K | Capacity: 30KVA/24KW 40K | Capacity: 40KVA/32KW 60K | Capacity: 60KVA/48KW 80K | Capacity: 80KVA/64KW 100K | Capacity: 100KVA/80KW 120K | Capacity: 120KVA/96KW | ||
Input | Nominal Voltage | 3 x 380VAC/ 400VAC (3Ph + N) | |
Acceptable Voltage Range | 285VAC – 475VAC | ||
Frequency | 50/60 Hz ±10% | ||
Inverter | Nominal Voltage | 3 x 380VAC/ 400VAC (3Ph + N) | |
Precision | Stationary: ±1% Transitory: ±5% (load variations 100-0-100%) | ||
Frequency | 50-60 Hz Synchronised ±1% With main absent ±0.1 Hz | ||
Max. Synchronisation Speed | ±1 Hz/s | ||
Waveform | Pure Sinewave | ||
Total Harmonic Distortion (THDv) | <2% (Linear Load); <5% (Non-Linear Load) | ||
Phase Displacement | 120° ±1% (Balance Load); 120° ±2% (Imbalances 50% of the Load) | ||
Dynamic Recovery Time | 3 Cycles at 90% of the Static Value | ||
Admissible Overload | 110% for 10min; 150% for 60sec; >160% for 200ms | ||
Admissible Crest Factor | 03:01 | ||
Admissible Power Factor | 0.6 – 1 (inductive or capacitive) | ||
Imbalance Output Voltage @100% Unbalanced Load | <1% | ||
Current Limit | High Overload, Short Circuit: RMS Voltage Limit High Crest Factor Current: Peak Voltage Limit | ||
Static Bypass | Type | Solid State | |
Voltage | 3 x 380VAC/ 400VAC (3Ph + N) | ||
Frequency | 50/60 Hz | ||
Activation Criterion | Microprocessor Control | ||
Transfer Time | Zero | ||
Admissible Overload | 150% for 1 hour; 180% for 30sec; >200% for 200ms | ||
Transfer to Bypass | Immediate for Overload >160% | ||
Retransfer | Automatic after Alarm Clear | ||
Maintenance Bypass | Type | Without Interruption | |
Voltage | 3 x 400V (3Ph + N) | ||
Frequency | 50/60 Hz | ||
Overall Efficiency | Line Mode | 10K and 15K : 90% 20K and 30K : 91% 40K and 60K : 92% 80K, 100K, and 120K : 93% | |
Battery Mode | 10K and 15K : 90% 20K and 30K : 91% 40K and 60K : 93% 80K, 100K, and 120K : 93% | ||
Battery and Charger | Battery Type and Numbers | 12VDC x 32 pcs (29 – 32 pcs Adjustable) | |
Nominal Battery Voltage | 384VDC (Based on 32 pcs Batteries) | ||
Charging Method | CC/ CV | ||
Charging Current | · 10K, 15K, and 20K : Default 10A; Max: Capacity/ Battery · 30K, 40K, 60K, 80K, 100K, and 120K : Default: 10A; Max. 40A | ||
Charging Voltage | Default: 10A; Max. 40A | ||
Physical | Dimension (D x W x H) | 10K and 15K : 656 x 405 x 817 20K: 656 x 405 x 941 30K and 40K: 821 x 432 x 1159 60K, 80K, and 100K: 975 x 554 x 1286 120K: 975 x 635 x 1326 | |
Net Weight (kgs) | 10K: 118 15K: 120 20K: 179 30K: 241 40K: 278 60K: 400 80K: 471 100K: 573 120K: 650 |